Greenheck kitchen ventilation service in the Twin Cities
Greenheck kitchen hood, rooftop exhaust fan and make-up air unit service in Minneapolis and Saint Paul, from the hood controls to the roof.
What do we service on a Greenheck kitchen ventilation system?
We service Greenheck hood lights, filters, controls, switches and interlocks, and the rooftop exhaust fans and make-up air units that serve them. Our technicians do the roof work; kitchen staff stay off the roof and just tell us what the hood is doing. Fire suppression and grease-duct cleaning stay with other trades.
Greenheck kitchen hoods
Greenheck started in 1947 as a small sheet metal shop in Schofield, Wisconsin, founded by Bob and Bernie Greenheck, and Schofield is still its corporate headquarters, with distribution centers in Dallas, Sacramento, Miami and Greensboro as well. Its own site calls it unique among suppliers of complete kitchen ventilation systems: hoods, fire suppression, utility distribution, fans and make-up air are all engineered to work together. Competing names on the same roofs and hood lines include CaptiveAire and Halton.
In Twin Cities kitchens a Greenheck system is typically a wall canopy hood on a full-service line, an island canopy over an open kitchen, a Type II heat and fume hood over a dish machine or oven, and an exhaust fan and make-up air unit on the roof above. The system is only as good as its slowest part. A hood that seems weak can be a clogged filter, a stopped fan or a make-up air unit that has shut down. Our page on kitchen hood and ventilation service covers the general approach, and fire suppression and grease-duct cleaning stay with other trades.
Reading the plate on Greenheck kitchen hood
Greenheck's fan manual says each fan carries a permanently affixed embossed metal nameplate with the model number and individual serial number, and its make-up air manual places the electrical and direct gas nameplates on the outside of the unit at the control panel side. Most of these sit outdoors, and staff should not go on the roof to read one; we read them when we are there. From the kitchen, have the hood type, the hood's own label and any control panel model ready.
Greenheck canopy, island and Type II hoods
Equipment guide
Seen on this line: Hood light out or flickering under the canopy / Filters bent, missing or loaded with grease / Hood-mounted control not starting the fan / Hood switch on but the exhaust fan not responding / Condensate gutter on a steam hood backing up
Greenheck's hood list includes a wall canopy, a four-sided island canopy with V-bank filters, a compact crossover hood with optional hood-mounted controls, and Type II heat and fume and steam and condensate hoods. The steam and condensate hood carries a gutter for dishwashers and kettles. Hood-mounted fan controls are the Greenheck-specific item we look at from the floor. Burned-out lights, damaged or missing filters, a sticky control switch and hood-mounted controls are our side of this equipment; where a hood carries integrated fire suppression, that suppression stays with the fire protection trade.
Greenheck CUE, CUBE and USGF upblast exhaust fans
Equipment guide
Seen on this line: Hood weak or noisy and the fan suspected / Wheel turning the wrong way after a power change / Grease trap or absorber overdue for cleaning / Belt squeal or loose belt on a CUBE / Disconnect or ground-level switch not responding
The CUE is a direct drive upblast fan rated 60 to 14,700 cfm, the CUBE is belt drive from 180 to 30,000 cfm, and the USGF is a belt drive fan for solid-fuel cooking with a non-stick coated wheel. Greenheck's manual requires the electrical supply to enter the motor compartment through the breather tube on kitchen installs and places the disconnect outside it, mounts the grease trough pointing down, and calls for a polypropylene grease trap with an absorber checked monthly. Belts get rechecked after 24 to 48 hours of running, and bearings take one or two shots of lithium grease yearly. All of that sits on the roof, and we service it there: our technicians go up for the fan, belts, bearings and trap, while kitchen staff stay on the floor and report what the hood is doing.
Greenheck DGX, IGX, KSQ and VSU make-up air
Equipment guide
Seen on this line: Make-up air not starting with the hood / Kitchen cold or doors hard to open from negative pressure / Burner lockout or gas pressure switch trip / Dirty filters starving a ground-level unit / Discharge temperature drifting from setpoint
The DGX is a direct gas-fired make-up air unit, the IGX is indirect gas-fired, the KSQ is a filtered, non-tempered supply fan, and the VSU is a vertical direct gas unit. The DGX manual puts the electrical nameplate and the gas nameplate on the outside of the unit at the control side, and describes high and low gas pressure switches that lock out the burner and need a manual reset. A fan interlock that is open stops heating. We check the interlock, control signals, filters and the burner's ignition and gas pressure switches on the unit itself, rooftop or ground level; building gas piping goes to a gas contractor.
Sourcing parts for Greenheck kitchen hood
Greenheck sells hoods, fans, make-up air, plenums, filters and controls as one family, so a replacement filter, light or control is specific to the hood series and size. Its fan manual lists specific accessories, such as a grease absorber with its own part number. Wheels, belts and bearings for a CUBE depend on the fan size printed on the nameplate.
Greenheck next to CaptiveAire and Halton
Compared with
Guides
More hoods and ventilation brands
Questions about Greenheck equipment
Why does my Greenheck hood not pull as strongly as it used to?
Check the filters first, since grease-loaded baffles choke airflow. Then check whether the make-up air has started, because a starved kitchen weakens a hood. If both are fine, the roof fan may have a slipped belt or reversed wheel, and we check that at the fan. Staff should never go on the roof; tell us what the hood is doing and we take it from there.
Do you work on the rooftop fan?
Yes. Our technicians service rooftop exhaust fans and make-up air units. Kitchen staff should never go on the roof to check one; tell us what the hood is doing, and we handle the fan, belts, bearings and controls.
What is a CUBE fan and why does the manual matter?
CUBE is Greenheck's belt drive upblast exhaust fan, rated up to 30,000 cfm. The maker's manual sets kitchen rules: power through the breather tube, the grease trough pointing down, a grease trap, and hinge hardware for cleaning access. On a weak-hood call we confirm from the kitchen side whether the fan is running and pulling; the breather tube, trough and hinge are checked at the fan itself.
What can kitchen staff check on a Greenheck hood?
Look at whether the filters are in place and not loaded with grease, whether the hood light and switch work, and whether the fan sounds like it is running. Then call. Staff stay off the roof and out of the control and electrical compartments, and duct cleaning remains a certified hood cleaning company's job.
Does a Greenheck make-up air unit need a gas technician?
It needs a technician, not kitchen staff. Direct gas units have a burner, gas train and high and low gas pressure switches that lock out and need a manual reset, and we test the ignition, pressure switches, interlock and controls on the unit. The building's gas piping and the utility meter go to a gas contractor.